What are the points of attention in the installation of diesel generator sets

Author:网站管理员 Sources:本站原创 Date:2016/5/28 11:20:12 Hits:1786 Belong to:Technology
We will encounter a lot of problems in the installation of diesel generating units, the following cited Jiang power to introduce the attention of the installation.
Whether it is a general generator, or diesel generator; whether it is leased to the generating unit, or to buy a generating unit, the price is very high. It is a big problem how to prolong the service life of the generator, and to make the generator to the maximum of the delivery rate. This article mentioned some of the problems that should be noticed when installing the generator, according to the experience of the production and life of the customer to solve the production and life of the long term.
1, the installation site should be well ventilated, the generator should have enough air inlet, the diesel engine should have a good outlet. Outlet area should be more than 1.5 times the area of the water tank.
2, around the installation should be kept clean, avoid placing in the vicinity of acid, alkali and other corrosive gases and vapors of items. Condition should be equipped with fire extinguisher.
3, in the indoor use, must be exhaust pipe conducting outdoor, diameter must is larger than or equal to that of the silencer a smoke tube diameter, connected to the pipeline elbows should not more than three, in order to ensure the smooth flow of the exhaust gas and the tube downward sloping 5-10 degrees, avoid rain water injection; if the exhaust pipe vertical upward installed, it must be equipped with rain cover.
4, based on the use of concrete, when the installation must be measured by the level of the level, so that the unit is fixed on the basis of the level. Between the unit and the foundation shall have a special cushion or foot bolt.
5, unit shell must have a reliable protective earthing, on the need to have neutral point grounding of the generator, it must be by a professional staff of neutral grounding and lightning protection devices, it is strictly prohibited to use city electricity connection device of neutral point earthing.
6, the generator and the city electric two-way switch must be very reliable, in order to prevent the power down. The connection reliability of the bidirectional switch should be recognized by the local power supply department.